| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | GEF-2A-4 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 20A-1P | 20A-1P | 20A-2P | | 8:00 AM | 15 A | | 2-12 AWG | 4:00 AM | SPECIFY CONDUCTORS | 125.00% | 2-12 AWG | 3-12 AWG | 4-12 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | EXHAUST FAN | MMS | | Louisville District | | | - | - | | | | 3:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 3:00 AM | 2:00 AM | | 1-12 AWG | SPECIFY GROUND | 1-12 AWG | | | | | | | | | GEF | 2A-4 | | | | | | | | | | 398 VA | M | 0 VA | 12:00 AM | 283 VA | 0 W | ROOF | | 0.0 | True | | | | | 250.00% | | | | | | | 1.0 | | | | | | 1.0 | | NORMAL | | | | | | | | | False | | | 20A-1P | 2-12 AWG | 3/4''C | 1-12 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | HVAC | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | False | False | 120 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | FCU-2A-4 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 20A-1P | 20A-1P | 20A-2P | | 6:00 AM | 15 A | | 2-12 AWG | 3:00 AM | SPECIFY CONDUCTORS | 125.00% | 2-12 AWG | 3-12 AWG | 4-12 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | FAN COIL UNIT | MMS | | Louisville District | | | - | - | | | | 3:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 3:00 AM | 2:00 AM | | 1-12 AWG | SPECIFY GROUND | 1-12 AWG | | | | | | | | | FCU | 2A-4 | | | | | | | | | | 702 VA | M | 0 VA | 12:00 AM | 500 VA | 0 W | REFER TO MECHANICAL DRAWINGS | | 0.0 | True | | | | | 250.00% | | | | | | | 1.0 | | | | | | 1.0 | | NORMAL | | | | | | | | | False | | | 20A-1P | 2-12 AWG | 3/4''C | 1-12 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | HVAC | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | False | False | 277 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | EF-2A-6 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 20A-1P | 20A-1P | 20A-2P | | 8:00 AM | 15 A | | 2-12 AWG | 4:00 AM | SPECIFY CONDUCTORS | 125.00% | 2-12 AWG | 3-12 AWG | 4-12 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | EXHAUST FAN | MMS* | | Louisville District | | | - | - | | | | 3:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 3:00 AM | 2:00 AM | | 1-12 AWG | SPECIFY GROUND | 1-12 AWG | | | | | | | | | EF | 2A-6 | | | | | | | | | | 398 VA | M | 0 VA | 12:00 AM | 283 VA | 0 W | ROOF | | 0.0 | True | | | | | 250.00% | | | | | | | 1.0 | | | | | | 1.0 | | NORMAL | | | | | | | | | False | | | 20A-1P | 2-12 AWG | 3/4''C | 1-12 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | HVAC | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | False | False | 120 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | GEF-2A-3 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 20A-1P | 20A-1P | 20A-2P | | 8:00 AM | 15 A | | 2-12 AWG | 4:00 AM | SPECIFY CONDUCTORS | 125.00% | 2-12 AWG | 3-12 AWG | 4-12 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | EXHAUST FAN | MMS | | Louisville District | | | - | - | | | | 3:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 3:00 AM | 2:00 AM | | 1-12 AWG | SPECIFY GROUND | 1-12 AWG | | | | | | | | | GEF | 2A-3 | | | | | | | | | | 398 VA | M | 0 VA | 12:00 AM | 283 VA | 0 W | ROOF | | 0.0 | True | | | | | 250.00% | | | | | | | 1.0 | | | | | | 1.0 | | NORMAL | | | | | | | | | False | | | 20A-1P | 2-12 AWG | 3/4''C | 1-12 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | HVAC | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | False | False | 120 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | EF-2A-5 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 20A-1P | 20A-1P | 20A-2P | | 11:00 AM | 15 A | | 2-12 AWG | 6:00 AM | SPECIFY CONDUCTORS | 125.00% | 2-12 AWG | 3-12 AWG | 4-12 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | EXHAUST FAN | MMS* | | Louisville District | | | - | - | | | | 4:00 AM | 2:00 AM | 4:00 AM | 4:00 AM | 2:00 AM | 12:00 AM | 12:00 AM | 1:00 AM | 1:00 AM | | 1-12 AWG | SPECIFY GROUND | 1-12 AWG | | | | | | | | | EF | 2A-5 | | | | | | | | | | 528 VA | M | 0 VA | 12:00 AM | 127 VA | 0 W | 1st FLOOR | | 0.0 | True | | | | | 250.00% | | | | | | | 1.0 | | | | | | 1.0 | | NORMAL | | | | | | | | | False | | | 20A-1P | 2-12 AWG | 3/4''C | 1-12 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | HVAC | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | False | False | 120 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | ACCU-2A-2 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 25A-1P | 25A-1P | 25A-2P | | 23 A | 25 A | | 2-12 AWG | 12:00 AM | SPECIFY CONDUCTORS | 125.00% | 2-12 AWG | 3-12 AWG | 4-12 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | AIR CONDITIONING OUTDOOR UNIT | FDS | | Louisville District | | | - | - | | | | 9:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | | 1-12 AWG | SPECIFY GROUND | 1-12 AWG | | | | | | | | | ACCU | 2A-2 | | | 1 | | | | | | | 1116 VA | M | 0 VA | 9:00 AM | 0 VA | 0 W | ROOF | | 0.0 | True | | | | | 250.00% | | | | | | | 1.0 | | | | | | 1.0 | | STANDBY | | | | | | | | | False | | | 25A-1P | 2-12 AWG | 3/4''C | 1-12 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | HVAC | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | True | False | 120 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | ACU-2A-2 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 20A-1P | 20A-1P | 20A-2P | | 2:00 AM | 15 A | | 2-12 AWG | 1:00 AM | SPECIFY CONDUCTORS | 125.00% | 2-12 AWG | 3-12 AWG | 4-12 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | AIR CONDITIONING INDOOR UNIT | FDS | | Louisville District | | | - | - | | | | 1:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | | 1-12 AWG | SPECIFY GROUND | 1-12 AWG | | | | | | | | | ACU | 2A-2 | | | 2 | | | | | | | 114 VA | M | 0 VA | 1:00 AM | 0 VA | 0 W | LEVEL 1 | | 0.0 | True | | | | | 250.00% | | | | | | | 1.0 | | | | | | 1.0 | | STANDBY | | | | | | | | | False | | | 20A-1P | 2-12 AWG | 3/4''C | 1-12 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | HVAC | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | True | False | 120 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | DHU-2A-1 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 35A-3P | | | 35A-3P | 32 A | 35 A | | 3-8 AWG | 32 A | SPECIFY CONDUCTORS | 125.00% | 2-8 AWG | 3-8 AWG | 4-8 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | DESSICANT DEHUMIDIFICATION UNIT HEATING COIL | VFD* | | Louisville District | | | - | - | | | | 25 A | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 25 A | 18 A | | 1-10 AWG | SPECIFY GROUND | 1-10 AWG | | | | | | | | | DHU | 2A-1 | | | | | | | | | | 21067 VA | M | 0 VA | 12:00 AM | 0 VA | 15000 W | ROOF | | 0.0 | True | | | | | 125.00% | | | | | | | 3.0 | | | | | | 3.0 | | NORMAL | | | | | | | | | False | | | 35A-3P | 3-8 AWG | 3/4''C | 1-10 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | HVAC | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | False | False | 480 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | BAF-2A-1 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 20A-3P | | | 20A-3P | 5:00 AM | 15 A | | 3-12 AWG | 3:00 AM | SPECIFY CONDUCTORS | 125.00% | 2-12 AWG | 3-12 AWG | 4-12 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | CEILING FAN | FDS | | Louisville District | | | - | - | | | | 2:00 AM | 7:00 AM | 2:00 AM | 16 A | 9:00 AM | 5:00 AM | 2:00 AM | 1:00 AM | 1:00 AM | | 1-12 AWG | SPECIFY GROUND | 1-12 AWG | | | | | | | | | BAF | 2A-1 | | | 1,3 | | | | | | | 1746 VA | M | 0 VA | 12:00 AM | 746 VA | 0 W | LEVEL 2 | | 0.0 | True | | | | | 250.00% | | | | | | | 3.0 | | | | | | 3.0 | | NORMAL | | | | | | | | | False | | | 20A-3P | 3-12 AWG | 3/4''C | 1-12 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | HVAC | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | False | False | 480 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | EF-2A-4 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 25A-1P | 25A-1P | 25A-2P | | 25 A | 25 A | | 2-12 AWG | 12:00 AM | SPECIFY CONDUCTORS | 125.00% | 2-12 AWG | 3-12 AWG | 4-12 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | EXHAUST FAN | MMS | | Louisville District | | | - | - | | | | 10:00 AM | 4:00 AM | 10:00 AM | 10:00 AM | 5:00 AM | 2:00 AM | 1:00 AM | 4:00 AM | 3:00 AM | | 1-12 AWG | SPECIFY GROUND | 1-12 AWG | | | | | | | | | EF | 2A-4 | | | 1 | | | | | | | 1176 VA | M | 0 VA | 12:00 AM | 373 VA | 0 W | ROOF | | 0.0 | True | | | | | 250.00% | | | | | | | 1.0 | | | | | | 1.0 | | NORMAL | | | | | | | | | False | | | 25A-1P | 2-12 AWG | 3/4''C | 1-12 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | HVAC | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | False | False | 120 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | EF-2A-3 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 20A-3P | | | 20A-3P | 3:00 AM | 15 A | | 3-12 AWG | 1:00 AM | SPECIFY CONDUCTORS | 125.00% | 2-12 AWG | 3-12 AWG | 4-12 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | EXHAUST FAN | FDS | | Louisville District | | | - | - | | | | 1:00 AM | 4:00 AM | 1:00 AM | 10:00 AM | 5:00 AM | 2:00 AM | 1:00 AM | 1:00 AM | 12:00 AM | | 1-12 AWG | SPECIFY GROUND | 1-12 AWG | | | | | | | | | EF | 2A-3 | | | 1 | | | | | | | 915 VA | M | 0 VA | 12:00 AM | 373 VA | 0 W | ROOF | | 0.0 | True | | | | | 250.00% | | | | | | | 3.0 | | | | | | 3.0 | | NORMAL | | | | | | | | | False | | | 20A-3P | 3-12 AWG | 3/4''C | 1-12 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | HVAC | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | False | False | 480 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | GEF-2A-1 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 20A-1P | 20A-1P | 20A-2P | | 11:00 AM | 15 A | | 2-12 AWG | 6:00 AM | SPECIFY CONDUCTORS | 125.00% | 2-12 AWG | 3-12 AWG | 4-12 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | EXHAUST FAN | MMS | | Louisville District | | | - | - | | | | 4:00 AM | 2:00 AM | 4:00 AM | 4:00 AM | 2:00 AM | 12:00 AM | 12:00 AM | 1:00 AM | 1:00 AM | | 1-12 AWG | SPECIFY GROUND | 1-12 AWG | | | | | | | | | GEF | 2A-1 | | | 1 | | | | | | | 528 VA | M | 0 VA | 12:00 AM | 127 VA | 0 W | ROOF | | 0.0 | True | | | | | 250.00% | | | | | | | 1.0 | | | | | | 1.0 | | NORMAL | | | | | | | | | False | | | 20A-1P | 2-12 AWG | 3/4''C | 1-12 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | HVAC | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | False | False | 120 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | GEF-2A-2 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 20A-1P | 20A-1P | 20A-2P | | 11:00 AM | 15 A | | 2-12 AWG | 6:00 AM | SPECIFY CONDUCTORS | 125.00% | 2-12 AWG | 3-12 AWG | 4-12 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | EXHAUST FAN | MMS | | Louisville District | | | - | - | | | | 4:00 AM | 2:00 AM | 4:00 AM | 4:00 AM | 2:00 AM | 12:00 AM | 12:00 AM | 1:00 AM | 1:00 AM | | 1-12 AWG | SPECIFY GROUND | 1-12 AWG | | | | | | | | | GEF | 2A-2 | | | 1 | | | | | | | 528 VA | M | 0 VA | 12:00 AM | 127 VA | 0 W | ROOF | | 0.0 | True | | | | | 250.00% | | | | | | | 1.0 | | | | | | 1.0 | | NORMAL | | | | | | | | | False | | | 20A-1P | 2-12 AWG | 3/4''C | 1-12 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | HVAC | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | False | False | 120 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | FCU-2A-2 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 20A-1P | 20A-1P | 20A-2P | | 8:00 AM | 15 A | | 2-12 AWG | 4:00 AM | SPECIFY CONDUCTORS | 125.00% | 2-12 AWG | 3-12 AWG | 4-12 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | FAN COIL UNIT | MMS | | Louisville District | | | - | - | | | | 3:00 AM | 3:00 AM | 3:00 AM | 7:00 AM | 4:00 AM | 12:00 AM | 12:00 AM | 1:00 AM | 1:00 AM | | 1-12 AWG | SPECIFY GROUND | 1-12 AWG | | | | | | | | | FCU | 2A-2 | | | | | | | | | | 831 VA | M | 0 VA | 12:00 AM | 246 VA | 0 W | LEVEL 1 | | 0.0 | True | | | | | 250.00% | | | | | | | 1.0 | | | | | | 1.0 | | NORMAL | | | | | | | | | False | | | 20A-1P | 2-12 AWG | 3/4''C | 1-12 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | HVAC | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | False | False | 277 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | 2A-GT-1 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 20A-3P | | | 20A-3P | 2:00 AM | 15 A | | 3-12 AWG | 1:00 AM | SPECIFY CONDUCTORS | 125.00% | 2-12 AWG | 3-12 AWG | 4-12 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | GLYCOL FILL PUMP | FDS | | Louisville District | | | - | - | | | | 1:00 AM | 3:00 AM | 12:00 AM | 7:00 AM | 4:00 AM | 12:00 AM | 12:00 AM | 1:00 AM | 1:00 AM | | 1-12 AWG | SPECIFY GROUND | 1-12 AWG | | | | | | | | | 2A-GT | 1 | | | - | | | | | | | 346 VA | M | 0 VA | 12:00 AM | 246 VA | 0 W | REFER TO PLUMBING DRAWINGS | | 0.0 | True | | | | | 250.00% | | | | | | | 3.0 | | | | | | 3.0 | | NORMAL | | | | | | | | | False | | | 20A-3P | 3-12 AWG | 3/4''C | 1-12 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | PLBG | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | False | False | 208 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | 2A-HWT-1 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 20A-3P | | | 20A-3P | 2:00 AM | 15 A | | 3-12 AWG | 1:00 AM | SPECIFY CONDUCTORS | 125.00% | 2-12 AWG | 3-12 AWG | 4-12 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | PRE-HEAT TANK & CIRCULATION PUMP | FDS | | Louisville District | | | - | - | | | | 1:00 AM | 3:00 AM | 12:00 AM | 7:00 AM | 4:00 AM | 12:00 AM | 12:00 AM | 1:00 AM | 1:00 AM | | 1-12 AWG | SPECIFY GROUND | 1-12 AWG | | | | | | | | | 2A-HWT | 1 | | | - | | | | | | | 346 VA | M | 0 VA | 12:00 AM | 246 VA | 0 W | REFER TO PLUMBING DRAWINGS | | 0.0 | True | | | | | 250.00% | | | | | | | 3.0 | | | | | | 3.0 | | NORMAL | | | | | | | | | False | | | 20A-3P | 3-12 AWG | 3/4''C | 1-12 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | PLBG | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | False | False | 208 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | 2A-CP-1 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 20A-3P | | | 20A-3P | 2:00 AM | 15 A | | 3-12 AWG | 1:00 AM | SPECIFY CONDUCTORS | 125.00% | 2-12 AWG | 3-12 AWG | 4-12 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | GLYCOL CIRCULATION PUMP | FDS | | Louisville District | | | - | - | | | | 1:00 AM | 3:00 AM | 12:00 AM | 7:00 AM | 4:00 AM | 12:00 AM | 12:00 AM | 1:00 AM | 1:00 AM | | 1-12 AWG | SPECIFY GROUND | 1-12 AWG | | | | | | | | | 2A-CP | 1 | | | - | | | | | | | 346 VA | M | 0 VA | 12:00 AM | 246 VA | 0 W | REFER TO PLUMBING DRAWINGS | | 0.0 | True | | | | | 250.00% | | | | | | | 3.0 | | | | | | 3.0 | | NORMAL | | | | | | | | | False | | | 20A-3P | 3-12 AWG | 3/4''C | 1-12 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | PLBG | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | False | False | 208 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | 2A-AC-2 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 20A-3P | | | 20A-3P | 19 A | 20 A | | 3-12 AWG | 10:00 AM | SPECIFY CONDUCTORS | 125.00% | 2-12 AWG | 3-12 AWG | 4-12 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | AIR COMPRESSOR | FDS | | Louisville District | | | - | - | | | | 8:00 AM | 23 A | 8:00 AM | 56 A | 31 A | 17 A | 8:00 AM | 6:00 AM | 4:00 AM | | 1-12 AWG | SPECIFY GROUND | 1-12 AWG | | | | | | | | | 2A-AC | 2 | | | - | | | | | | | 6319 VA | M | 0 VA | 12:00 AM | 3728 VA | 0 W | REFER TO PLUMBING DRAWINGS | | 0.0 | True | | | | | 250.00% | | | | | | | 3.0 | | | | | | 3.0 | | NORMAL | | | | | | | | | False | | | 20A-3P | 3-12 AWG | 3/4''C | 1-12 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | PLBG | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | False | False | 480 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | 2A-AC-1 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 35A-3P | | | 35A-3P | 35 A | 35 A | | 3-12 AWG | 18 A | SPECIFY CONDUCTORS | 125.00% | 2-12 AWG | 3-12 AWG | 4-12 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | AIR COMPRESSOR | FDS | | Louisville District | | | - | - | | | | 14 A | 41 A | 14 A | 100 A | 55 A | 31 A | 14 A | 13 A | 9:00 AM | | 1-12 AWG | SPECIFY GROUND | 1-12 AWG | | | | | | | | | 2A-AC | 1 | | | - | | | | | | | 11639 VA | M | 0 VA | 12:00 AM | 7457 VA | 0 W | REFER TO PLUMBING DRAWINGS | | 0.0 | True | | | | | 250.00% | | | | | | | 3.0 | | | | | | 3.0 | | NORMAL | | | | | | | | | False | | | 35A-3P | 3-12 AWG | 3/4''C | 1-12 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | PLBG | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | False | False | 480 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | JP-1 2 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 20A-3P | | | 20A-3P | 9:00 AM | 15 A | | 3-12 AWG | 4:00 AM | SPECIFY CONDUCTORS | 125.00% | 2-12 AWG | 3-12 AWG | 4-12 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | JOCKEYPUMP | FDS | | Louisville District | | | - | - | | | | 3:00 AM | 10:00 AM | 3:00 AM | 24 A | 13 A | 8:00 AM | 3:00 AM | 3:00 AM | 2:00 AM | | 1-12 AWG | SPECIFY GROUND | 1-12 AWG | | | | | | | | | JP | 2A-1 | | | 9 | | | | | | | 2827 VA | M | 0 VA | 12:00 AM | 1491 VA | 0 W | LEVEL 1 | | 0.0 | True | | | | | 250.00% | | | | | | | 3.0 | | | | | | 3.0 | | NORMAL | | | | | | | | | False | | | 20A-3P | 3-12 AWG | 3/4''C | 1-12 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | PLBG | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | False | False | 480 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | FP-1 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 250A-3P | | | 250A-3P | 240 A | 250 A | | 3-1 AWG | 120 A | SPECIFY CONDUCTORS | 125.00% | 2-1 AWG | 3-1 AWG | 4-1 AWG | 1 1/2''C | SPECIFY CONDUIT | 1 1/4''C | 1 1/2''C | | | | | Vanderweil Engineers | | | | FIRE PUMP | ATS | | Louisville District | | | - | - | | | | 96 A | 12:00 AM | 96 A | 12:00 AM | 12:00 AM | 211 A | 96 A | 94 A | 67 A | | 1-4 AWG | SPECIFY GROUND | 1-4 AWG | | | | | | | | | FP | 2A-1 | | | 10 | | | | | | | 79813 VA | M | 0 VA | 12:00 AM | 55927 VA | 0 W | LEVEL 1 | | 0.0 | True | | | | | 250.00% | | | | | | | 3.0 | | | | | | 3.0 | | EMERG | | | | | | | | | False | | | 250A-3P | 3-1 AWG | 1 1/2''C | 1-4 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | PLBG | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | False | False | 480 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | CACCU-2A-1 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 35A-2P | 35A-1P | 35A-2P | | 34 A | 35 A | | 2-12 AWG | 17 A | SPECIFY CONDUCTORS | 125.00% | 2-12 AWG | 3-12 AWG | 4-12 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | AIR CONDITIONING OUTDOOR UNIT | FDS | | Louisville District | | | - | - | | | | 13 A | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | | 1-12 AWG | SPECIFY GROUND | 1-12 AWG | | | | | | | | | CACCU | 2A-1 | | | 1 | | | | | | | 2787 VA | M | 0 VA | 13 A | 0 VA | 0 W | ROOF | | 0.0 | True | | | | | 250.00% | | | | | | | 1.0 | | | | | | 2.0 | | STANDBY | | | | | | | | | False | | | 35A-2P | 2-12 AWG | 3/4''C | 1-12 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | HVAC | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | True | False | 208 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | AHU-2A-1 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 125A-3P | | | 125A-3P | 120 A | 125 A | | 3-4 AWG | 60 A | SPECIFY CONDUCTORS | 125.00% | 2-4 AWG | 3-4 AWG | 4-4 AWG | 1 1/4''C | SPECIFY CONDUIT | 1''C | 1 1/4''C | | | | | Vanderweil Engineers | | | | AIR HANDLING UNIT | VFD* | | Louisville District | | | - | - | | | | 48 A | 12:00 AM | 27 A | 12:00 AM | 12:00 AM | 59 A | 27 A | 12:00 AM | 12:00 AM | | 1-6 AWG | SPECIFY GROUND | 1-6 AWG | | | | | | | | | AHU | 2A-1 | | | | | | | | | | 39906 VA | M | 0 VA | 48 A | 14914 VA | 47555 W | ROOF | | 0.0 | True | | | | | 250.00% | | | | | | | 3.0 | | | | | | 3.0 | | NORMAL | | | | | | | | | False | | | 125A-3P | 3-4 AWG | 1 1/4''C | 1-6 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | HVAC | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | True | False | 480 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | UH-2A-1 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 20A-1P | 20A-1P | 20A-2P | | 12:00 AM | 15 A | | 2-12 AWG | 12:00 AM | SPECIFY CONDUCTORS | 125.00% | 2-12 AWG | 3-12 AWG | 4-12 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | UNIT HEATER | MMS | | Louisville District | | | - | - | | | | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | | 1-12 AWG | SPECIFY GROUND | 1-12 AWG | | | | | | | | | UH | 2A-1 | | | 1,3 | | | | | | | 13 VA | M | 0 VA | 12:00 AM | 0 VA | 9 W | LEVEL 1 | | 0.0 | True | | | | | 250.00% | | | | | | | 1.0 | | | | | | 1.0 | | NORMAL | | | | | | | | | False | | | 20A-1P | 2-12 AWG | 3/4''C | 1-12 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | HVAC | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | False | False | 120 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | 2A-SP-1 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 20A-1P | 20A-1P | 20A-2P | | 9:00 AM | 15 A | | 2-12 AWG | 4:00 AM | SPECIFY CONDUCTORS | 125.00% | 2-12 AWG | 3-12 AWG | 4-12 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | SUMP PUMP | WP RECEPT. | | Louisville District | | | - | - | | | | 3:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 3:00 AM | 2:00 AM | | 1-12 AWG | SPECIFY GROUND | 1-12 AWG | | | | | | | | | 2A-SP | 1 | | | - | | | | | | | 419 VA | M | 0 VA | 12:00 AM | 298 VA | 0 W | REFER TO PLUMBING DRAWINGS | | 0.0 | True | | | | | 250.00% | | | | | | | 1.0 | | | | | | 1.0 | | NORMAL | | | | | | | | | False | | | 20A-1P | 2-12 AWG | 3/4''C | 1-12 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | PLBG | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | False | False | 120 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | CS-2B-1 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 70A-3P | | | 70A-3P | 68 A | 70 A | | 3-8 AWG | 34 A | SPECIFY CONDUCTORS | 125.00% | 2-8 AWG | 3-8 AWG | 4-8 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | CONDENSATE DRAIN PUMP | FDS | | Louisville District | | | - | - | | | | 27 A | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | | 1-8 AWG | SPECIFY GROUND | 1-8 AWG | | | | | | | | | CS | 2B-1 | | | | | | | | | | 22447 VA | M | 0 VA | 27 A | 0 VA | 0 W | LEVEL 2 | | 0.0 | True | | | | | 250.00% | | | | | | | 3.0 | | | | | | 3.0 | | NORMAL | | | | | | | | | False | | | 70A-3P | 3-8 AWG | 3/4''C | 1-8 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | HVAC | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | True | False | 480 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | SCP-2A-1 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 20A-1P | 20A-1P | 20A-2P | | 4:00 AM | 15 A | | 2-12 AWG | 2:00 AM | SPECIFY CONDUCTORS | 125.00% | 2-12 AWG | 3-12 AWG | 4-12 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | STEAM CONDENSATE PUMP | MMS | | Louisville District | | | - | - | | | | 2:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | | 1-12 AWG | SPECIFY GROUND | 1-12 AWG | | | | | | | | | SCP | 2A-1 | | | | | | | | | | 180 VA | M | 0 VA | 2:00 AM | 0 VA | 1 W | LEVEL 1 | | 0.0 | True | | | | | 250.00% | | | | | | | 1.0 | | | | | | 1.0 | | NORMAL | | | | | | | | | False | | | 20A-1P | 2-12 AWG | 3/4''C | 1-12 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | HVAC | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | True | False | 120 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | ACCU-2A-1 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 35A-2P | 35A-1P | 35A-2P | | 33 A | 35 A | | 2-12 AWG | 16 A | SPECIFY CONDUCTORS | 125.00% | 2-12 AWG | 3-12 AWG | 4-12 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | AIR CONDITIONING OUTDOOR UNIT | FDS | | Louisville District | | | - | - | | | | 13 A | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | | 1-12 AWG | SPECIFY GROUND | 1-12 AWG | | | | | | | | | ACCU | 2A-1 | | | 1 | | | | | | | 2704 VA | M | 0 VA | 13 A | 0 VA | 0 W | ROOF | | 0.0 | True | | | | | 250.00% | | | | | | | 1.0 | | | | | | 2.0 | | NORMAL | | | | | | | | | False | | | 35A-2P | 2-12 AWG | 3/4''C | 1-12 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | HVAC | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | True | False | 208 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | P-2A-2 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 20A-3P | | | 20A-3P | 3:00 AM | 15 A | | 3-12 AWG | 1:00 AM | SPECIFY CONDUCTORS | 125.00% | 2-12 AWG | 3-12 AWG | 4-12 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | PUMP | FDS | | Louisville District | | | - | - | | | | 1:00 AM | 4:00 AM | 1:00 AM | 10:00 AM | 5:00 AM | 2:00 AM | 1:00 AM | 1:00 AM | 12:00 AM | | 1-12 AWG | SPECIFY GROUND | 1-12 AWG | | | | | | | | | P | 2A-2 | | | 1 | | | | | | | 915 VA | M | 0 VA | 12:00 AM | 373 VA | 0 W | LEVEL 2 | | 0.0 | True | | | | | 250.00% | | | | | | | 3.0 | | | | | | 3.0 | | STANDBY | | | | | | | | | False | | | 20A-3P | 3-12 AWG | 3/4''C | 1-12 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | HVAC | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | False | False | 480 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | P-2A-1 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 20A-3P | | | 20A-3P | 3:00 AM | 15 A | | 3-12 AWG | 1:00 AM | SPECIFY CONDUCTORS | 125.00% | 2-12 AWG | 3-12 AWG | 4-12 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | PUMP | FDS | | Louisville District | | | - | - | | | | 1:00 AM | 4:00 AM | 1:00 AM | 10:00 AM | 5:00 AM | 2:00 AM | 1:00 AM | 1:00 AM | 12:00 AM | | 1-12 AWG | SPECIFY GROUND | 1-12 AWG | | | | | | | | | P | 2A-1 | | | 1 | | | | | | | 915 VA | M | 0 VA | 12:00 AM | 373 VA | 0 W | LEVEL 2 | | 0.0 | True | | | | | 250.00% | | | | | | | 3.0 | | | | | | 3.0 | | STANDBY | | | | | | | | | False | | | 20A-3P | 3-12 AWG | 3/4''C | 1-12 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | HVAC | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | False | False | 480 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | P-2A-3 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 20A-1P | 20A-1P | 20A-2P | | 15 A | 15 A | | 2-12 AWG | 7:00 AM | SPECIFY CONDUCTORS | 125.00% | 2-12 AWG | 3-12 AWG | 4-12 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | PUMP | MMS | | Louisville District | | | - | - | | | | 6:00 AM | 2:00 AM | 6:00 AM | 6:00 AM | 3:00 AM | 12:00 AM | 12:00 AM | 2:00 AM | 2:00 AM | | 1-12 AWG | SPECIFY GROUND | 1-12 AWG | | | | | | | | | P | 2A-3 | | | 1 | | | | | | | 696 VA | M | 0 VA | 12:00 AM | 186 VA | 0 W | LEVEL 2 | | 0.0 | True | | | | | 250.00% | | | | | | | 1.0 | | | | | | 1.0 | | STANDBY | | | | | | | | | False | | | 20A-1P | 2-12 AWG | 3/4''C | 1-12 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | HVAC | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | False | False | 120 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | CP-2A-1 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 20A-1P | 20A-1P | 20A-2P | | 12:00 AM | 15 A | | 2-12 AWG | 12:00 AM | SPECIFY CONDUCTORS | 125.00% | 2-12 AWG | 3-12 AWG | 4-12 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | CONDENSATE DRAIN PUMP | MMS | | Louisville District | | | - | - | | | | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | | 1-12 AWG | SPECIFY GROUND | 1-12 AWG | | | | | | | | | CP | 2A-1 | | | 3 | | | | | | | 21 VA | M | 0 VA | 12:00 AM | 15 VA | 0 W | LEVEL 2 | | 0.0 | True | | | | | 250.00% | | | | | | | 1.0 | | | | | | 1.0 | | NORMAL | | | | | | | | | False | | | 20A-1P | 2-12 AWG | 3/4''C | 1-12 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | HVAC | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | False | False | 120 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | CUH-2A-1 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 20A-1P | 20A-1P | 20A-2P | | 15 A | 20 A | | 2-12 AWG | 1:00 AM | SPECIFY CONDUCTORS | 125.00% | 2-12 AWG | 3-12 AWG | 4-12 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | CABINENT UNIT HEATER | MMS | | Louisville District | | | - | - | | | | 1:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 1:00 AM | 12:00 AM | | 1-12 AWG | SPECIFY GROUND | 1-12 AWG | | | | | | | | | CUH | 2A-1 | | | 1 | | | | | | | 73 VA | M | 0 VA | 12:00 AM | 52 VA | 0 W | LEVEL 1 | | 0.0 | True | | | | | 2500.00% | | | | | | | 1.0 | | | | | | 1.0 | | NORMAL | | | | | | | | | False | | | 20A-1P | 2-12 AWG | 3/4''C | 1-12 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | HVAC | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | False | False | 120 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | AD-2A-1 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 20A-3P | | | 20A-3P | 19 A | 20 A | | 3-12 AWG | 10:00 AM | SPECIFY CONDUCTORS | 125.00% | 2-12 AWG | 3-12 AWG | 4-12 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | AIR CURTAIN | FDS | | Louisville District | | | - | - | | | | 8:00 AM | 23 A | 8:00 AM | 56 A | 31 A | 17 A | 8:00 AM | 6:00 AM | 4:00 AM | | 1-12 AWG | SPECIFY GROUND | 1-12 AWG | | | | | | | | | AD | 2A-1 | | | 3 | | | | | | | 6319 VA | M | 0 VA | 12:00 AM | 3728 VA | 0 W | LEVEL 1 | | 0.0 | True | | | | | 250.00% | | | | | | | 3.0 | | | | | | 3.0 | | NORMAL | | | | | | | | | False | | | 20A-3P | 3-12 AWG | 3/4''C | 1-12 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | HVAC | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | False | False | 480 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | FCU-2A-6 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 20A-1P | 20A-1P | 20A-2P | | 8:00 AM | 15 A | | 2-12 AWG | 4:00 AM | SPECIFY CONDUCTORS | 125.00% | 2-12 AWG | 3-12 AWG | 4-12 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | FAN COIL UNIT | MMS | | Louisville District | | | - | - | | | | 3:00 AM | 3:00 AM | 3:00 AM | 7:00 AM | 4:00 AM | 12:00 AM | 12:00 AM | 1:00 AM | 1:00 AM | | 1-12 AWG | SPECIFY GROUND | 1-12 AWG | | | | | | | | | FCU | 2A-6 | | | | | | | | | | 831 VA | M | 0 VA | 12:00 AM | 246 VA | 0 W | LEVEL 1 | | 0.0 | True | | | | | 250.00% | | | | | | | 1.0 | | | | | | 1.0 | | NORMAL | | | | | | | | | False | | | 20A-1P | 2-12 AWG | 3/4''C | 1-12 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | HVAC | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | False | False | 277 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | KEF-2A-2 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 20A-3P | | | 20A-3P | 8:00 AM | 15 A | | 3-12 AWG | 4:00 AM | SPECIFY CONDUCTORS | 125.00% | 2-12 AWG | 3-12 AWG | 4-12 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | FAN | VFD | | Louisville District | | | - | - | | | | 3:00 AM | 8:00 AM | 3:00 AM | 20 A | 11:00 AM | 7:00 AM | 3:00 AM | 2:00 AM | 1:00 AM | | 1-12 AWG | SPECIFY GROUND | 1-12 AWG | | | | | | | | | KEF | 2A-2 | | | | | | | | | | 2494 VA | M | 0 VA | 12:00 AM | 1119 VA | 0 W | ROOF | | 0.0 | True | | | | | 250.00% | | | | | | | 3.0 | | | | | | 3.0 | | NORMAL | | | | | | | | | False | | | 20A-3P | 3-12 AWG | 3/4''C | 1-12 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | HVAC | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | False | False | 480 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | EF-2A-2 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 20A-3P | | | 20A-3P | 1:00 AM | 15 A | | 3-12 AWG | 1:00 AM | SPECIFY CONDUCTORS | 125.00% | 2-12 AWG | 3-12 AWG | 4-12 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | EXHAUST FAN | FDS | | Louisville District | | | - | - | | | | 12:00 AM | 3:00 AM | 12:00 AM | 7:00 AM | 4:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | | 1-12 AWG | SPECIFY GROUND | 1-12 AWG | | | | | | | | | EF | 2A-2 | | | 1 | | | | | | | 346 VA | M | 0 VA | 12:00 AM | 246 VA | 0 W | ROOF | | 0.0 | True | | | | | 250.00% | | | | | | | 3.0 | | | | | | 3.0 | | NORMAL | | | | | | | | | False | | | 20A-3P | 3-12 AWG | 3/4''C | 1-12 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | HVAC | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | False | False | 480 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | TEF-2A-1 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 20A-3P | | | 20A-3P | 3:00 AM | 15 A | | 3-12 AWG | 1:00 AM | SPECIFY CONDUCTORS | 125.00% | 2-12 AWG | 3-12 AWG | 4-12 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | FAN | FDS | | Louisville District | | | - | - | | | | 1:00 AM | 4:00 AM | 1:00 AM | 10:00 AM | 5:00 AM | 2:00 AM | 1:00 AM | 1:00 AM | 12:00 AM | | 1-12 AWG | SPECIFY GROUND | 1-12 AWG | | | | | | | | | TEF | 2A-1 | | | | | | | | | | 915 VA | M | 0 VA | 12:00 AM | 373 VA | 0 W | ROOF | | 0.0 | True | | | | | 250.00% | | | | | | | 3.0 | | | | | | 3.0 | | NORMAL | | | | | | | | | False | | | 20A-3P | 3-12 AWG | 3/4''C | 1-12 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | HVAC | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | False | False | 480 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | KEF-2A-3 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 20A-3P | | | 20A-3P | 9:00 AM | 15 A | | 3-12 AWG | 4:00 AM | SPECIFY CONDUCTORS | 125.00% | 2-12 AWG | 3-12 AWG | 4-12 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | FAN | VFD | | Louisville District | | | - | - | | | | 3:00 AM | 10:00 AM | 3:00 AM | 24 A | 13 A | 8:00 AM | 3:00 AM | 3:00 AM | 2:00 AM | | 1-12 AWG | SPECIFY GROUND | 1-12 AWG | | | | | | | | | KEF | 2A-3 | | | | | | | | | | 2827 VA | M | 0 VA | 12:00 AM | 1491 VA | 0 W | ROOF | | 0.0 | True | | | | | 250.00% | | | | | | | 3.0 | | | | | | 3.0 | | NORMAL | | | | | | | | | False | | | 20A-3P | 3-12 AWG | 3/4''C | 1-12 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | HVAC | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | False | False | 480 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | KEF-2A-1 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 60A-3P | | | 60A-3P | 53 A | 60 A | | 3-10 AWG | 26 A | SPECIFY CONDUCTORS | 125.00% | 2-10 AWG | 3-10 AWG | 4-10 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | FAN | VFD | | Louisville District | | | - | - | | | | 21 A | 12:00 AM | 21 A | 12:00 AM | 12:00 AM | 46 A | 21 A | 19 A | 13 A | | 1-10 AWG | SPECIFY GROUND | 1-10 AWG | | | | | | | | | KEF | 2A-1 | | | | | | | | | | 17459 VA | M | 0 VA | 12:00 AM | 11185 VA | 0 W | ROOF | | 0.0 | True | | | | | 250.00% | | | | | | | 3.0 | | | | | | 3.0 | | NORMAL | | | | | | | | | False | | | 60A-3P | 3-10 AWG | 3/4''C | 1-10 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | HVAC | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | False | False | 480 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | EF-2A-1 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 20A-3P | | | 20A-3P | 3:00 AM | 15 A | | 3-12 AWG | 1:00 AM | SPECIFY CONDUCTORS | 125.00% | 2-12 AWG | 3-12 AWG | 4-12 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | EXHAUST FAN | FDS | | Louisville District | | | - | - | | | | 1:00 AM | 4:00 AM | 1:00 AM | 10:00 AM | 5:00 AM | 2:00 AM | 1:00 AM | 1:00 AM | 12:00 AM | | 1-12 AWG | SPECIFY GROUND | 1-12 AWG | | | | | | | | | EF | 2A-1 | | | 1 | | | | | | | 915 VA | M | 373 VA | 12:00 AM | 373 VA | 0 W | ROOF | | 0.0 | True | | | | | 250.00% | | | | | | | 3.0 | | | | | | 3.0 | | NORMAL | | | | | | | | | False | | | 20A-3P | 3-12 AWG | 3/4''C | 1-12 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | HVAC | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | False | False | 480 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | FCU-2A-8 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 20A-1P | 20A-1P | 20A-2P | | 6:00 AM | 15 A | | 2-12 AWG | 3:00 AM | SPECIFY CONDUCTORS | 125.00% | 2-12 AWG | 3-12 AWG | 4-12 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | FAN COIL UNIT | MMS | | Louisville District | | | - | - | | | | 3:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 3:00 AM | 2:00 AM | | 1-12 AWG | SPECIFY GROUND | 1-12 AWG | | | | | | | | | FCU | 2A-8 | | | | | | | | | | 702 VA | M | 0 VA | 12:00 AM | 500 VA | 0 W | LEVEL 1 | | 0.0 | True | | | | | 250.00% | | | | | | | 1.0 | | | | | | 1.0 | | NORMAL | | | | | | | | | False | | | 20A-1P | 2-12 AWG | 3/4''C | 1-12 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | HVAC | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | False | False | 277 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | CACU-2A-1 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 20A-1P | 20A-1P | 20A-2P | | 8:00 AM | 15 A | | 2-12 AWG | 4:00 AM | SPECIFY CONDUCTORS | 125.00% | 2-12 AWG | 3-12 AWG | 4-12 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | COMPUTER ROOM AIR CONDITIONING UNIT | DS | | Louisville District | | | - | - | | | | 3:00 AM | 3:00 AM | 3:00 AM | 7:00 AM | 4:00 AM | 12:00 AM | 12:00 AM | 1:00 AM | 1:00 AM | | 1-12 AWG | SPECIFY GROUND | 1-12 AWG | | | | | | | | | CACU | 2A-1 | | | 1 | | | | | | | 831 VA | M | 0 VA | 12:00 AM | 246 VA | 0 W | REFER TO MECHANICAL DRAWINGS | | 0.0 | True | | | | | 250.00% | | | | | | | 1.0 | | | | | | 1.0 | | STANDBY | | | | | | | | | False | | | 20A-1P | 2-12 AWG | 3/4''C | 1-12 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | HVAC | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | False | False | 277 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | FCU-2A-9 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 20A-1P | 20A-1P | 20A-2P | | 6:00 AM | 15 A | | 2-12 AWG | 3:00 AM | SPECIFY CONDUCTORS | 125.00% | 2-12 AWG | 3-12 AWG | 4-12 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | FAN COIL UNIT | MMS | | Louisville District | | | - | - | | | | 3:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 3:00 AM | 2:00 AM | | 1-12 AWG | SPECIFY GROUND | 1-12 AWG | | | | | | | | | FCU | 2A-9 | | | | | | | | | | 702 VA | M | 0 VA | 12:00 AM | 500 VA | 0 W | LEVEL 1 | | 0.0 | True | | | | | 250.00% | | | | | | | 1.0 | | | | | | 1.0 | | NORMAL | | | | | | | | | False | | | 20A-1P | 2-12 AWG | 3/4''C | 1-12 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | HVAC | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | False | False | 277 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | ACU-2A-1 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 20A-2P | 20A-1P | 20A-2P | | 1:00 AM | 15 A | | 2-12 AWG | 1:00 AM | SPECIFY CONDUCTORS | 125.00% | 2-12 AWG | 3-12 AWG | 4-12 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | AIR CONDITIONING INDOOR UNIT | FDS | | Louisville District | | | - | - | | | | 1:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | | 1-12 AWG | SPECIFY GROUND | 1-12 AWG | | | | | | | | | ACU | 2A-1 | | | 2 | | | | | | | 119 VA | M | 0 VA | 1:00 AM | 0 VA | 0 W | LEVEL 1 | | 0.0 | True | | | | | 250.00% | | | | | | | 1.0 | | | | | | 2.0 | | NORMAL | | | | | | | | | False | | | 20A-2P | 2-12 AWG | 3/4''C | 1-12 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | HVAC | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | True | False | 208 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | FCU-2A-3 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 20A-1P | 20A-1P | 20A-2P | | 6:00 AM | 15 A | | 2-12 AWG | 3:00 AM | SPECIFY CONDUCTORS | 125.00% | 2-12 AWG | 3-12 AWG | 4-12 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | FAN COIL UNIT | MMS | | Louisville District | | | - | - | | | | 3:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 3:00 AM | 2:00 AM | | 1-12 AWG | SPECIFY GROUND | 1-12 AWG | | | | | | | | | FCU | 2A-3 | | | 3 | | | | | | | 702 VA | M | 0 VA | 12:00 AM | 500 VA | 0 W | REFER TO MECHANICAL DRAWINGS | | 0.0 | True | | | | | 250.00% | | | | | | | 1.0 | | | | | | 1.0 | | NORMAL | | | | | | | | | False | | | 20A-1P | 2-12 AWG | 3/4''C | 1-12 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | HVAC | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | False | False | 277 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | MAU-2A-1 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | 90A-3P | 90A-3P | | | 250A-3P | 230 A | 250 A | | 3-2 AWG | 115 A | SPECIFY CONDUCTORS | 125.00% | 2-2 AWG | 3-2 AWG | 4-2 AWG | 1 1/4''C | SPECIFY CONDUIT | 1 1/4''C | 1 1/4''C | | | | | Vanderweil Engineers | | | | MAKE UP AIR UNIT | VFD | | Louisville District | | | - | - | | | | 92 A | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | 12:00 AM | | 1-4 AWG | SPECIFY GROUND | 1-4 AWG | | | | | | | | | MAU | 2A-1 | | | | | | | | | | 76487 VA | M | 0 VA | 92 A | 0 VA | 0 W | ROOF | | 0.0 | True | | | | | 250.00% | | | | | | | 3.0 | | | | | | 3.0 | | NORMAL | | | | | | | | | False | | | 90A-3P | 3-2 AWG | 1 1/4''C | 1-4 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | HVAC | | Loadable Family | | USACE_Electrical Fixtures.rvt | True | False | False | True | False | 480 V | | | | | | | | | |
| MechanicalEquipmentScheduler_USACE | Electrical Fixtures | HVU-2A-1 | True | False | | | | | | | | | | | | | | | | | | | | | | | | False | SPECIFY BREAKER | 100A-3P | | | 100A-3P | 95 A | 100 A | | 3-6 AWG | 48 A | SPECIFY CONDUCTORS | 125.00% | 2-6 AWG | 3-6 AWG | 4-6 AWG | 3/4''C | SPECIFY CONDUIT | 3/4''C | 3/4''C | | | | | Vanderweil Engineers | | | | HEATING & VENTILATION SUPPLY FAN | VFD | | Louisville District | | | - | - | | | | 38 A | 12:00 AM | 27 A | 12:00 AM | 12:00 AM | 59 A | 27 A | 25 A | 18 A | | 1-8 AWG | SPECIFY GROUND | 1-8 AWG | | | | | | | | | HVU | 2A-1 | | | | | | | | | | 31593 VA | M | 0 VA | 38 A | 14914 VA | 0 W | ROOF | | 0.0 | True | | | | | 250.00% | | | | | | | 3.0 | | | | | | 3.0 | | NORMAL | | | | | | | | | False | | | 100A-3P | 3-6 AWG | 3/4''C | 1-8 AWG | SEE ELECTRICAL FLOOR PLANS | 1.0 | | | | | | | | | | | | | | | | | | | | | | | | | HVAC | | Loadable Family | | USACE_Electrical Fixtures.rvt | False | False | False | True | False | 480 V | | | | | | | | | |